Product details
| Part number | 4098-5268 |
|---|---|
| Description | MX Triple Sensor + Isolator |
| Category | Detectors & Bases / Smoke, Heat & Multi Sensors |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4100ES (MX Loop Module), 4010ES (MX Loop Module), 4007ES (MX Loop Module) |
| Approvals | UL listed; smoke sensors listed to UL 268 |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-5268
The 4098-5268 is an MX addressable triple sensor that combines photoelectric smoke, heat and CO sensing, with a built-in isolator. It monitors smoke, heat and CO levels at the same time to decide whether a fire is present, and is meant for life safety applications and locations where conditions challenge standard sensors. It works with Simplex 4100ES, 4010ES and 4007ES control units fitted with an MX Loop Module.
Indoor use only, with a narrower operating range of 33.8°F to 111.2°F (1°C to 44°C).
Specifications
| UL-listed smoke sensitivity | 2.23 ±1.75 %/ft |
|---|---|
| Current | 350 µA supervisory; 4.0 mA maximum in alarm |
| Operating temperature | 33.8°F to 111.2°F (1°C to 44°C) |
| Storage temperature | -4°F to 131°F (-20°C to 55°C) |
| Humidity | Up to 93% RH non-condensing |
| IP rating | IP44 in accordance with BS EN 60529:1992 + A2:2013 |
| Dimensions | 108 mm x 42 mm (4.252 in. x 1.653 in.) |
| Communications | MX Loop, one address for each sensor base |
Used with
- 4098-5260 – 4 in. continuity base 4B-C
- 4098-5217 – Addressable loop-powered sounder base
- 4098-5220 – Addressable loop-powered sounder-beacon base
- 2098-9808 – Remote LED alarm indicator
- 4098-5276 – Address flags (pack of 100)
From Simplex datasheet S4906-0017. The datasheet and UL listing can be downloaded under Documents above.