Product details
| Part number | 4098-9683 |
|---|---|
| Description | 4098-9683 Detector Base with Relay |
| Category | Detectors & Bases / Detector Bases & Sounder Bases |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | Conventional 2-wire initiating device circuits (IDCs), 4090-9101 and 4090-9106 Zone Adapter Modules (IDNet or MAPNET II) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9683
Two-wire base for Simplex 4098 conventional smoke and heat detectors, with a built-in auxiliary alarm relay (dual Form C contacts) whose module mounts in the base electrical box. With smoke detectors such as the 4098-9602 it also has connections for a remote LED indicator. It must be the only device on its initiating device circuit (IDC) for the relay to operate.
The relay mounts in the base box, so use a 4” octagonal or square box with a 1-1/2” extension ring.
Specifications
| Relay contacts | Dual Form “C” contacts, for suppressed loads |
|---|---|
| Relay rating, power limited | 1 A @ 28 VDC |
| IDC connections | Screw terminals for 18 to 14 AWG (zone +), color coded 18 AWG leads (zone –) |
| Relay connections | Color coded 18 AWG leads |
| Electrical box | 4” octagonal or 4” square box, 1-1/2” deep with 1-1/2” deep extension ring |
| Devices per IDC | One (only device on the IDC) |
Used with
- 4098-9602 – TrueAlarm photoelectric detector with TrueSense heat detection
- 4098-9601 – Photoelectric smoke detector
- 4098-9612 – Heat detector, 135° F (57° C) fixed temperature
- 4098-9615 – Heat detector, 200° F (93° C) with rate-of-rise
- 4098-9832 – Adapter plate for surface or semi-flush mounting
From Simplex datasheet S4098-0014. The datasheet and installation manual can be downloaded under Documents above.