Product details
| Part number | 4098-XAD-210 |
|---|---|
| Description | Dual Zn Sampl Unt with Kit&sensor |
| Category | Detectors & Bases / Aspirating & Duct Sampling |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4007ES, 4008, 4010, 4010ES, 4100ES and 4100U (IDNet), Panels with MAPNET II communications |
| Approvals | UL listed to Standard 268A; ULC listed to Standard S529; CSFM approved |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-XAD-210
Air aspiration duct smoke detection unit with two inlets and two TrueAlarm photoelectric sensors (one per inlet), supplied with the dual-inlet duct probe kit (LF-42243). A fan draws air from the duct through sampling tubes and a filter to the sensors, so the housing can be mounted away from the duct; it is the model for ducts wider than 90 in. (2286 mm). It reports over IDNet or MAPNET II with one address per sensor and needs a separate 24 VDC supply.
Dual-inlet duct detection needs three single-core flexible tubes, 25 ft or 50 ft each, ordered separately.
Specifications
| Supply voltage | 18 VDC to 30 VDC supplied from fire alarm system |
|---|---|
| Current | 110 mA to 300 mA depending on fan speed; 680 mA in-rush |
| Communications | IDNet or MAPNET II communications, one address for each sensor |
| Sampling pipe | Remote housing up to 82 ft (25 m) with rigid pipe, or 50 ft (15 m) with flexible tubing |
| Sensor sensitivity | 0.5% and 1.0% for each foot of obscuration, selectable at host control unit |
| Air velocity range | 0 to 4000 ft/min (0 to 1220 m/min) |
| Operating temperature range | 32°F to 122°F (0°C to 50°C) |
| Remote relays | Supervised control of up to 15 4098-9843 relays |
Used with
- LF-42288 – Sampling tube kit, two inlet tubes, ducts up to 27 in. (686 mm)
- LF-42249 – 50 ft (15 m) flexible single-core tubing
- LF-42283 – Dual-inlet water trap kit for humid environments
- 2098-9806 – Remote test station with key switch and red LED
- 4098-9843 – Remote relay, single Form C
From Simplex datasheet S4098-0048. The datasheet can be downloaded under Documents above.