Part no. 4098-XAD-200

Dual Zn Smplg Unt with Sg Sensor

8,168.45 SAR 8,168.45 SAR

8,168.45 SAR incl. VAT
  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4098-XAD-200
DescriptionDual Zn Smplg Unt with Sg Sensor
CategoryDetectors & Bases / Aspirating & Duct Sampling
System Simplex TrueAlarm detectors and TrueAlert appliances
Works with4007ES, 4008, 4010, 4010ES, 4100ES and 4100U (IDNet), Panels with MAPNET II communications
ApprovalsUL listed to Standard 268A (duct use); ULC listed to Standard S529; CSFM approved
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4098-XAD-200

Air aspiration smoke detection housing with two inlets and two TrueAlarm photoelectric sensors, one for each zone or pipe run, supplied as the housing only; the sampling pipe is ordered separately. It is used for open areas where spot detectors are not practical, such as prison cells, transformer vaults, cable tunnels and MRI rooms, and covers up to 3600 square feet. It reports over IDNet or MAPNET II with one address per sensor and needs a separate 24 VDC supply.

For open area use it does not meet the requirements of the 7th edition of UL 268.

Specifications

Supply voltage18 VDC to 30 VDC supplied from fire alarm system
Current110 mA to 300 mA depending on fan speed; 680 mA in-rush
CommunicationsIDNet or MAPNET II communications, one address for each sensor
Sampling pipeUp to 82 ft (25 m) of pipe on each run; maximum two sampling holes for each inlet
Sensor sensitivity1.5% to 3.0% for each foot of obscuration, selectable at host control unit
Air velocity range0 to 4000 ft/min (0 to 1220 m/min)
Operating temperature range32°F to 122°F (0°C to 50°C)
Remote relaysSupervised control of up to 15 4098-9843 relays

Used with

  • 2098-9808 – Remote red LED status indicator
  • 2098-9806 – Remote test station with key switch and red LED
  • 4098-9843 – Remote relay, single Form C
  • 4098-XAD-100 – Single-inlet version, one sensor

From Simplex datasheet S4098-0048. The datasheet can be downloaded under Documents above.