Skip to Content
Part no. 5000-031

Additional 5000 Head and Prism

6,542.35 SAR 6,542.35 SAR

6,542.35 SAR incl. VAT
  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number5000-031
DescriptionAdditional 5000 Head and Prism
CategoryDetectors & Bases / Beam Detectors
System Simplex fire alarm systems
Works with4098-9019 / 4098-9020 IDNet addressable beam detector controller
ApprovalsUL 268 and ULC-S529 listed (beam detector system)
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 5000-031

Additional reflective detector head with prism for the Simplex IDNet addressable beam smoke detector system. One extra head can be added to each 4098-9019 system, so one controller runs two heads. The head's infrared beam is reflected back by the prism, and the head rotates to align itself with the prism center during installation.

Only one additional head can be added to each 4098-9019 system.

Specifications

Dimensions (HxWxD)5 9/32 in. x 5 5/16 in. x 5 9/32 in. (135 mm x 134 mm x 132 mm)
Operating distance range26 ¼ ft. to 330 ft (8 m to 100 m)
Beam optical wavelength850 nm
HousingFlame Retardant ABS, IP rating = IP54
Wiring, controller to head328 ft (100 m) maximum distance, use twisted wire pair; 18 AWG to 16 AWG
Beam status LEDNormal = Green; Alarm = Red; Fault (Trouble) = Yellow

Used with

  • 4098-9020 – Beam detector controller
  • 5000-201 – Adjustment bracket for motorized reflective detector heads
  • 1210-000 – Detector surface mount Uni-Box
  • 1220-000 – Cover plate to mount the head to a double gang box
  • 1000-018 – Protective wire cage for 5000 series detector heads

From Simplex datasheet S4098-0049. The datasheet can be downloaded under Documents above.