Skip to Content
Part no. 4098-9773

520HZ Sounder Base with CO

863.65 SAR 863.65 SAR

863.65 SAR incl. VAT
  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4098-9773
Description520HZ Sounder Base with CO
CategoryDetectors & Bases / Detector Bases & Sounder Bases
System Simplex TrueAlarm detectors and TrueAlert appliances
Works with4007ES, 4010ES and 4100ES (IDNet, software revision 2.01.02 or higher), 4100U (software revision 12.05 or higher)
ApprovalsListed to UL 268, UL 464, UL 2075, ULC-S529 and CSA 6.19-01; CSFM listed; FM approved
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4098-9773

TrueAlarm addressable sensor base with a carbon monoxide (CO) sensor and a low-frequency 520 Hz sounder, for IDNet circuits. A TrueAlarm photoelectric (4098-9714), multi-sensor (4098-9764) or heat sensor (4098-9733) fits on the base, and the base uses one IDNet address. The sounder needs separate 24 VDC system power or a NAC; with the 4905-9835 module it can sound temporal code 3 for fire or temporal code 4 for CO.

The base must be flush mounted, and a sensor head is ordered separately.

Specifications

Sounder output, 520 Hz signal79.5 dBA minimum at 10 ft (3 m) per UL 464; 85.5 dBA per UL 268 and CSA 6.19-01
Sounder voltage24 VDC nominal, 16 VDC to 32 VDC from NAC
Alarm current, sounder on (520 Hz)129 mA at 16 V, 115 mA at 18 V
CommunicationsIDNet communications, 1 address for each base
CO sensor life10 year operational lifetime, 5 years for 4100U FACUs
Operating temperature range32°F to 122°F (0°C to 50°C)
Humidity range10% to 95% RH
MountingFlush mounting required; minimum box depth 1 1/2 in. (38 mm)

Used with

  • 4098-9714 – TrueAlarm photoelectric smoke sensor
  • 4098-9764 – TrueAlarm multi-sensor, photoelectric and heat
  • 4098-9733 – TrueAlarm heat sensor
  • 4098-9747 – CO replacement cartridge (CORC)
  • 4905-9835 – Temporal Code Module for TC3/TC4 coding from a NAC

From Simplex datasheet S4098-0053. The datasheet can be downloaded under Documents above.