Product details
| Part number | 4098-9688 |
|---|---|
| Description | Duct Detector Hous 2-W with Relay Dr |
| Category | Detectors & Bases / Aspirating & Duct Sampling |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | Conventional 2-wire IDCs of Simplex fire alarm panels, 2004FS and 2008FS Foundation Series control units, 4090-5260 MX Zone Adapter Module (1 per ZAM) |
| Approvals | UL listed to Standard 268A; ULC and CSFM listed; FM approved |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9688
Duct smoke detector housing with a factory-installed 4098-9601 TrueAlarm photoelectric detector, for conventional 2-wire initiating device circuits (IDCs). It is powered from the IDC and gives a supervised output for one 4098-9841 remote relay, which is included. A sampling tube sized to the duct width is ordered separately.
It must be the only device on its IDC for the relay to operate; on 4004 or 4005 panels connect it to a high current IDC.
Specifications
| Operating voltage | 18-32 VDC, from compatible IDC |
|---|---|
| Standby current | 2 mA @ 24 VDC (includes relay supervision current) |
| Alarm current | 40 mA maximum @ 24 VDC |
| Relay | 4098-9841 only, one maximum; dual Form C, 1 A @ 28 VDC, 1/2 A @ 120 VAC, resistive |
| Relay location | 100 ft (30 m) maximum to relay coil; relay within 3 ft (1 m) of device being controlled |
| Air velocity range | 300 to 4000 ft/min (91 to 1220 m/min) |
| Duct size | Minimum 8” (203 mm) square or 18” (457 mm) diameter |
| Housing | Black ABS base with clear polycarbonate cover |
Used with
- 4098-9841 – Remote relay, dual Form C (included)
- 4098-9830 – Red LED alarm indicator
- 4098-9834 – Test station with keyswitch and red LED
- 4098-9855 – Sampling tube for 13” to 23” duct width
- 4098-9856 – Sampling tube for 24” to 46” duct width
From Simplex datasheet S4098-0029. The datasheet can be downloaded under Documents above.