Skip to Content
Part no. 4098-5211

4 Wire Sounder Base

1.15 SAR 1.15 SAR

  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4098-5211
Description4 Wire Sounder Base
CategoryDetectors & Bases / Detector Bases & Sounder Bases
System Simplex TrueAlarm detectors and TrueAlert appliances
Works with4100ES (MX Loop), 4010ES (MX Loop), 4100U (MX Loop)
ApprovalsUL listed
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4098-5211

Sounder base for MX Technology sensors that is switched on from the MX Loop but powered from a separate 24 VDC fire alarm power supply through its own wiring loop. It gives up to 90 dBA at 10 ft (3 m), with eight local tones selected by DIP switch and volume adjustable at the base.

It needs a separate 24 VDC power wiring loop in addition to the MX Loop.

Specifications

PowerSeparate 24 VDC fire alarm power supply through a separate wiring loop
Sounder base voltage18 to 32 VDC from fire alarm power supply. 24 VDC is nominal
Maximum sound output90 dBA at 10 ft (3 m)
Current5 µA supervisory; 20 µA from MX Loop; 20 mA from external 24 VDC power at full volume
TonesEight tone selections, DIP switch selected at the base
Operating temperature0° to 38° C (32° to 100° F)
Size with sensor mounted110 mm x 68.5 mm (4 11/32 in. x 2 11/16 in.)
Installation instructions579-926

Used with

  • 4098-5201 – MX heat sensor
  • 4098-5202 – MX photoelectric smoke sensor
  • 4098-5203 – MX photoelectric smoke sensor with heat sensor
  • 517.050.015 – Volume Trimmer Tool

From Simplex datasheet S4098-0045. The datasheet can be downloaded under Documents above.