Product details
| Part number | 3000-103 |
|---|---|
| Description | FIRERAY3000 End to End Beam Smoke Detect |
| Category | Detectors & Bases / Beam Detectors |
| System | Simplex fire alarm systems |
| Works with | Conventional 4-wire fire alarm control panels (24 VDC) |
| Approvals | UL listed to UL 268; ULC and CSFM listed (listings by Fire Fighting Enterprises) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 3000-103
End-to-end infrared optical beam smoke detector by Fire Fighting Enterprises, with a separate transmitter and receiver and a ground-level controller with LCD. The set includes one transmitter, one receiver and one controller; one controller can serve two transmitter/receiver pairs (add a 3000-016 pack). Range is 16.5 ft to 393 ft (5 m to 120 m), and the receiver has a built-in laser for alignment.
Suitable where the beam path is narrow or the building has reflective surfaces.
Specifications
| Operating distance | 16.5 ft to 393 ft (5 m to 120 m) |
|---|---|
| Input voltage | 12 to 36 VDC +/- 10%; from a compatible and agency listed fire alarm power supply |
| Controller current | 14 mA, with one or two receivers |
| Transmitter current | 8 mA per Transmitter |
| Alarm and trouble relays | Dedicated, separate Form C relays, rated 2 A @ 30 VDC resistive |
| Sensitivity | 25% to 60% obscuration selectable in 1% increments |
| UL listed temperature range | -4° F to 131° F (-20° C to 55° C); non-condensing |
| Housing | UL94V2 PC; IP rating = IP54 |
Used with
- 3000-016 – Additional detector pack, transmitter and receiver
- 3000-201 – Adjustment bracket
- 3000-202 – Surface mount adapter
- 3000-209 – Control back box
- 1000-018 – Wire cage
From Simplex datasheet S4098-0050. The datasheet can be downloaded under Documents above.