Product details
| Part number | 4090-9119 |
|---|---|
| Description | Relay IDNet 2 IAM with Feedback |
| Category | Addressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators) |
| System | Simplex fire alarm systems |
| Works with | 4007ES (IDNet), 4010ES (IDNet), 4100ES (IDNet), 4100U (IDNet, software revision 11 or higher) |
| Approvals | UL listed to UL 864; ULC and CSFM listed; FM approved; MEA (NYC) acceptance |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4090-9119
Single-address IDNet module with one Form C relay output and one unsupervised input for a normally open dry contact. It is typically used for fan control with status feedback, for example from a sail switch or pressure switch. Power comes from the IDNet channel, so no separate power wiring is needed.
The relay is set to OFF at power-up and when IDNet communication is lost.
Specifications
| Communications | IDNet communications, one address; one unit load |
|---|---|
| Relay | Form C (SPDT): 2 A @ 30 VDC resistive; 0.5 A @ 120 VAC resistive |
| Input | Normally open dry contacts, up to 500 ft (152 m), indoor wiring only |
| Point type | FRIAM |
| Wire connections | Screw terminals, 18 to 14 AWG |
| Dimensions | 4-1/8” H x 4-1/8” W x 1-3/8” D (105 mm x 105 mm x 35 mm) |
| Mounting | Standard 4” square electrical box |
| Temperature / humidity | 32° to 120° F (0° to 49° C) indoor operation only; 10 to 90% RH at 90° F (32° C) |
Used with
- 4090-9813 – Adapter plate for 4 11/16 in. (119 mm) square box
- 4090-9801 – Trim plate with LED window, semi-flush box
- 4090-9802 – Trim plate with LED window, surface box
- 2081-9044 – Overvoltage protector
From Simplex datasheet S4090-0008. The datasheet can be downloaded under Documents above.