Part number4090-9101
DescriptionZAM Class B Monitor, IDNet
CategoryAddressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators)
System Simplex fire alarm systems
Works with4007ES (IDNet), 4008 (IDNet), 4010 (IDNet), 4010ES (IDNet), 4100ES (IDNet), 4100U (IDNet), 4100/4100U, 4120, 4020 and 2120 CDTs (MAPNET II)
ApprovalsUL listed to Standard 864; ULC and CSFM listed (CSFM 7300-0026:223); FM approved; MEA (NYC) acceptance (MEA35-93E)
AvailabilityIn stock in Riyadh
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4090-9101

Zone adapter module that lets one IDNet or MAPNET II address monitor a conventional Class B initiating device circuit (IDC). It works with 2-wire or 4-wire initiating devices and has power reset connections for 4-wire devices. It mounts in a standard 4" (102 mm) square electrical box.

Zone device power is supplied separately, typically from the fire alarm control panel.

Specifications

CommunicationsIDNet or MAPNET II, 1 address per device
ZAM input voltage18.9 to 32 VDC (nominal 24 VDC)
ZAM current @ 24 VDCSupervisory = 16 mA maximum; Alarm = 72 mA maximum
Zone supervision resistor3.3 k, 1 W
Wire connectionsScrew terminals for in/out wiring, 18 to 14 AWG wire (0.82 to 2.08 mm²)
Dimensions4 ⅛” H x 4 ⅛” W x 1 ⅜” D (105 mm x 105 mm x 35 mm)
Mounting4" (102 mm) square box, 2-1/8" (54 mm) minimum depth
Temperature / humidity32° to 120° F (0° to 49° C), intended for indoor operation; up to 93% RH at 100° F (38° C)

Used with

  • 4081-9002 – 3.3 k end-of-line resistor harness for Class B zone monitoring
  • 4090-9801 – Trim plate with LED viewing window, for semi-flush mounted box
  • 4090-9802 – Trim plate with LED viewing window, for surface mounted box
  • 4090-9813 – Adapter plate to fit 4 11⁄16” (119 mm) square electrical box
  • 2081-9044 – Overvoltage protectors

From Simplex datasheet 4090-0003. The datasheet, UL listing and installation manual can be downloaded under Documents above.