Product details
| Part number | 4090-9006 |
|---|---|
| Description | Sup Release Periph & Enclosure |
| Category | Addressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators) |
| System | Simplex fire alarm systems |
| Works with | 4100ES (with Suppression Releasing Appliqué), 4100U (software revision 11.05 or higher), IDNet, 4009 IDNet NAC Extender |
| Approvals | UL, ULC, CSFM listed; FM approved; MEA (NYC) acceptance; CSFM Listing 7300-0026:313 (SRP); this boxed model is the one required for ULC listing |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4090-9006
The 4090-9006 is a Suppression Release Peripheral (SRP) supplied in a NEMA 1 red box with an LED indicator on the door. With a 4100ES (or 4100U) panel it controls and supervises the actuators of automatic extinguishing, deluge and preaction sprinkler release systems. A release needs both an IDNet command and an active NAC (dual command control), and the unit provides one releasing appliance circuit (RAC).
Each releasing circuit takes one 24 VDC actuator (or two 12 VDC actuators in series) and needs a 2081-9046 coil supervision module in the actuator wiring junction box.
Specifications
| Communications | IDNet, one address |
|---|---|
| RAC output rating | 2 A maximum with 4100ES; 1 A maximum with 4009 IDNet NAC Extender (at nominal 24 VDC, regulated) |
| NAC input voltage | 16 to 32 VDC (nominal 24 VDC) |
| Supervisory current | No additional current required, circuit appears as standard end-of-line (EOL) NAC loading |
| Wire connections | Screw terminals for input and output wiring, 18 to 12 AWG wire (0.82 mm² to 3.31 mm²) |
| IDNet wiring distance | Up to 2500 ft (762 m) from the IDNet source module |
| Operating temperature | 32° F to 120° F (0° C to 49° C) indoor operation only |
| Enclosure | NEMA 1 red box, LED indicator on front of door |
Used with
- 2081-9046 – Coil supervision module, required, one per RAC
- 4010-9830 – Suppression Releasing Appliqué (English), required for 4100ES releasing
- 2080-9056 – Abort switch, flush mount
- 2080-9057 – Abort switch, surface mount
- 2081-9044 – Overvoltage protector for IDNet wiring
From Simplex datasheet 4100-0040. The datasheet can be downloaded under Documents above.