| Part number | 4090-5205 |
|---|---|
| Description | Monitor ZAM |
| Category | Addressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators) |
| System | Simplex fire alarm systems |
| Works with | 4100ES with MX Loop Module, 4010ES with MX Loop Module, 4100U with MX Loop Module |
| Approvals | UL listed to Standard 864 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4090-5205
Addressable MX Technology module that connects conventional low-voltage detectors and callpoints to the MX Loop. It provides monitoring and zone power for two Class B circuits or one Class A circuit. Zone power comes from a 4100-5130 Voltage Regulator Module in the host panel, and power reset is controlled from the MX Loop module.
Needs regulated 24 VDC from a 4100-5130 Voltage Regulator Module; check two-wire detector compatibility in the installation instructions.
Specifications
| Inputs | Two Class B inputs or one Class A input |
|---|---|
| Input voltage | Nominal voltage = 24 VDC; minimum voltage = 21.9 VDC; maximum voltage = 26.4 VDC |
| Current from MX Loop | Class B standby = 0.28 mA; Class A standby = 0.53 mA |
| Current from external 24 VDC supply | Class B standby = 14 mA; Class A standby = 8.25 mA; Class B or Class A alarm = 50 mA per detector (spur) circuit |
| Detector voltage | Minimum detector voltage = 18 VDC; maximum detector voltage = 25 V |
| Detector load / end-of-line | Maximum standby detector load per 4090-5205 = 2.8 mA; End-of-Line Resistor for Class B spur circuits = 4.7 kΩ |
| Maximum circuit resistance | 50 Ω |
| Operating temperature | 32° F to 120° F (0° C to 49° C) |
Used with
- 4100-5130 – Voltage Regulator Module in the host panel, for regulated 24 VDC
- 4081-9021 – 4.7 kΩ end-of-line resistor harness, for Class A input
- 517.035.007 – Replacement module front cover
- 516.800.918 – MX Service Tool, ref. MX Model 801AP