About the 4090-5203

Addressable MX Technology module with a single relay output, controlled from the MX Loop. It is used to signal fire conditions to plant, machinery, fire doors, dampers and security systems. The relay contact is rated 2 A @ 24 VDC and the relay coil is monitored.

Needs a 4100ES, 4010ES or 4100U panel fitted with an MX Loop Module.

Specifications

Relay contact2 A @ 24 VDC
MX Loop current0.5 mA in standby; 4.5 mA in alarm
Address settingProgrammed with the MX Service Tool
Mounting boxStandard 2-gang MK box
Wiring connectionsTerminal blocks, for wire size 20 to 14 AWG (0.5 to 2.5 mm²)
Operating temperature32° F to 120° F (0° C to 49° C)
Humidityup to 93% RH at 90° F (32° C)

Used with

  • 517.035.007 – Replacement module front cover
  • 516.800.918 – MX Service Tool, ref. MX Model 801AP

From Simplex datasheet S4090-0012. The datasheet, UL listing and installation manual can be downloaded under Documents above.