Product details
| Part number | 4098-9822 |
|---|---|
| Description | Truealarm Relay Module |
| Category | Addressable Modules & Interfaces / Relays & Interface Modules |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | TrueAlarm sensor bases with remote LED/relay connections |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9822
Unsupervised relay that follows the LED of a TrueAlarm sensor base and switches when the base LED is on steady, meaning a local alarm or trouble. It has DPDT contacts and needs external 24 VDC coil power. It mounts in the base electrical box.
The relay is unsupervised and needs a separate 24 VDC supply.
Specifications
| Contacts | DPDT, for resistive or suppressed loads |
|---|---|
| Contact rating | 2 A at 30 VDC; 1/2 A at 120 VAC |
| Coil power | External 24 VDC |
| Size | 2 1/2 in. x 1 1/2 in. x 1 in. (64 mm x 38 mm x 25.4 mm), 3.75 cubic inches |
| Mounting | In base electrical box; 4 in. square or octagonal box with 1 1/2 in. extension ring |
Used with
- 4098-9794 – TrueAlarm sounder base
- 4098-9789 – Sensor base with connections for remote LED or unsupervised relay, white
- 4098-9775 – Sensor base with connections for remote LED or unsupervised relay, black
- 4098-9791 – Four-wire sensor supervised relay base
From Simplex datasheet S4098-0019. The datasheet can be downloaded under Documents above.