Product details
| Part number | 49AV-WRFO-BA |
|---|---|
| Description | Weatherproof Addressable Horn/Strobe Wall Red Fire (BA) |
| Category | Notification Appliances / TrueAlert ES Addressable Appliances |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4100ES with EPS+ or EPS Power Supply (IDNAC), 4007ES with IDNAC Notification, 4010ES with ESS Enhanced System Supply (IDNAC), 4009 IDNAC Repeater |
| Approvals | UL 1971 (indoor, 15 or 75 cd); UL 1638 (outdoor, WP75 or WP185); horn UL 464; CSFM; FM approved |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 49AV-WRFO-BA
UL listed weatherproof TrueAlert ES addressable horn/strobe for wall mounting indoors or outdoors, with a red cover, white FIRE lettering and clear lens. It is powered, supervised and controlled from an IDNAC signaling line circuit; strobe intensity is set from the panel or by jumper to 15 or 75 cd indoors (UL 1971) or WP75 or WP185 outdoors (UL 1638). It must be mounted on a matching weatherproof box, ordered separately; models ending in -BA are assembled in the USA.
The weatherproof mounting box 49WPBB-AVVOWR (red) or 49WPBB-AVVOWW (white) is required and is ordered separately.
Specifications
| Strobe intensity | 15 or 75 cd (UL 1971, indoor); WP75 or WP185 (UL 1638, outdoor) |
|---|---|
| Operating voltage | 23 VDC to 31 VDC, Special Application |
| Current at 23 VDC, horn on continuous, high | 80 mA (15 cd), 165 mA (75 cd), 163 mA (WP75), 189 mA (WP185); 238 mA (WP75) and 274 mA (WP185) below 32°F |
| Temperature range | 32° to 120° F (0° to 49° C) at 15 or 75 cd; -31°F to 150°F (-35° C to 66°C) at WP75 or WP185 |
| Humidity range | 10% to 93%, at 100° F (38° C) (UL 1971); up to 98%, at 104 °F (40° C) (UL 1638) |
| Horn output, UL 464, steady/high | 81.3 dB at 10 ft (3 m), 23 VDC |
| Enclosure | NEMA 3R |
| Wiring | Terminal blocks for 18 AWG to 12 AWG (0.82 mm² to 3.31 mm²) |
Used with
- 49WPBB-AVVOWR – Red surface mount weatherproof mounting box (required)
- 49AVC-WRFIRE-O – Separate red A/V weatherproof cover, FIRE wording
- 4905-9929 – TrueAlert addressable wiring isolator
From Simplex datasheet S49WP-0001. The datasheet can be downloaded under Documents above.