Product details
| Part number | 4100-9816 |
|---|---|
| Description | Master Clock Interface Kit |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES, 4100U, 6500 Time Control Center (via 6400-9568), RS-232 interfaces that answer QT and QD requests |
| Approvals | UL, ULC, CSFM listed; FM approved; MEA (NYC) acceptance |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-9816
Single-slot module with two RS-232 ports for 4100ES and 4100U panels. Port B keeps the panel time in step with a building master clock, such as a 6500 Time Control Center through the 6400-9568 BCD Code Converter; port A serves printers, terminals or other peripherals. A 4.5 ft (1.4 m) DB-25 RS-232 cable is included.
Specifications
| Ports | Dual RS-232; port A for peripherals, port B for master clock |
|---|---|
| Current | 132 mA @ 24 VDC standby and alarm |
| Mounting | Single slot motherboard/daughter card, in an expansion bay |
| Connections | DB-25 plugs and terminal blocks; 4.5 ft (1.4 m) cable included |
| Operating temperature | 32 °F to 120 °F (0 °C to 49 °C) |
| Humidity | Up to 93% RH, non-condensing @ 90 °F (32 °C) |
Used with
- 6400-9568 – BCD Code Converter for master time control centers
From Simplex datasheet S4100-0033. The datasheet can be downloaded under Documents above.