Product details
| Part number | 4100-9601 |
|---|---|
| Description | Local Mode Transponder |
| Category | Fire Alarm Control Panels / 4100ES Panels & Bays |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES (RUI) |
| Approvals | UL, ULC, CSFM listed; FM approved; UL 864, UL 1076, UL 2017, UL 1730, UL 2572, CAN/ULC-S527, CAN/ULC-S559 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-9601
A 4100ES MINIPLEX transponder with local mode. It includes the bay with power distribution interface and a 4100-0625 Local Mode Transponder Interface Module, and links to the host panel over RUI up to 2500 ft (762 m). If communication with the host is lost, it runs default fire alarm operation for its own devices and appliances.
Alarms reset at a Local Mode Controller during local mode are not sent to the host panel when communication returns.
Specifications
| Current, normal | 38 mA supervisory; 38 mA alarm |
|---|---|
| Current, in local mode | 23 mA supervisory; 23 mA alarm |
| Host communications | RUI, up to 2500 ft (762 m) |
| Includes | Bay equipment with power distribution interface, and 4100-0625 Local Mode Transponder Interface Module mounted in Block A |
| Local mode, photoelectric sensors | Alarm at 3.7%/ft smoke obscuration |
| Local mode, heat sensors | Alarm at 135 °F (57 °C) |
| Local mode, notification | Sound a general alarm temporal pattern horn tone |
Used with
- 4601-9109 – Local Mode Controller, surface mount, red
- 4601-9110 – Local Mode Controller, flush mount, beige
- 4100-5401 – ES-PS power supply
- 4100-0633 – Door Tamper Switch
- 4100-0635 – PDM for 220/230/240 VAC systems
From Simplex datasheet S4100-1035. The datasheet and installation manual can be downloaded under Documents above.