| Part number | 4100-3109 |
|---|---|
| Description | IDNET2 Module 250PT 2 Loop Isolator |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES (ES-PS), IDNet 2 devices and TrueAlarm sensors |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-3109
Addressable IDNet 2 channel module for the 4100ES, with an electrically isolated output and two short circuit isolating loops wired Class B or Class A for up to 250 points. It supports IDNet devices and TrueAlarm sensors, including QuickConnect and QuickConnect2, and is standard on the ES-PS with IDNet 2 module.
A maximum of 20 devices with LED on is supported for each channel.
Specifications
| Capacity | 250 points |
|---|---|
| Output | Electrically isolated, two short circuit isolating Class B or Class A loops |
| Size | 1 block |
| Current, no devices | 50 mA standby; 60 mA alarm |
| Current, 250 devices | 250 mA standby; 350 mA alarm (includes 20 device LEDs in alarm) |
| Distance from panel | 1 to 125 devices: 4000 ft (1219 m), 50 ohms; 126 to 250 devices: 2500 ft (762 m), 35 ohms |
| Total wire length with T-taps | Up to 12,500 ft (3.8 km), 0.60 μF |
| Wire | Unshielded twisted pair (UTP) for new installation; terminals for 18 to 12 AWG |
Used with
- 4100-3111 – IDNet Short Circuit Isolating Loop Output Module (up to two per 4100-3109)
- 4100-3110 – IDNet 2+2 Module, four isolating loops
From Simplex datasheet S4100-1031. The datasheet can be downloaded under Documents above.