Product details
| Part number | 4100-1333 |
|---|---|
| Description | DIG100W Amplifier, 6NAC, 220VAC, 70V |
| Category | Fire Fighter Telephones & Voice / Voice Evacuation Audio & Amplifiers |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES |
| Approvals | UL |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-1333
A 100 W digital primary amplifier with its own power supply for 4100ES emergency voice/alarm systems. It has a 70.7 VRMS output, runs from 220/230/240 VAC, 50/60 Hz, and includes six Class B audio NACs. It is constant supervision compatible.
Only one 100 W amplifier can be mounted in each expansion bay.
Specifications
| Output power | 100 W |
|---|---|
| Output voltage | 70.7 VRMS |
| Power supply input | 220/230/240 VAC, 50/60 Hz |
| Audio NACs | Six, Class B |
| NAC rating | 50 W or 100 speakers maximum; 1.4 A @ 70.7 VRMS |
| Type | Digital, constant supervision compatible |
| Mounting | Blocks E, F, G & H; 1 max/bay |
Used with
- 4100-1339 – Backup 100 W digital amplifier, 70.7 VRMS, 220/230/240 VAC
- 4100-1248 – 100 W Amplifier Expansion NAC Module (six more Class B NACs)
- 4100-1249 – 100 W Class A Adapter Module
- 4100-1260 – Constant Supervision Adapter, 70.7 VRMS (two for the six NACs)
From Simplex datasheet S4100-1035. The datasheet can be downloaded under Documents above.