Product details
| Part number | 4100-1272 |
|---|---|
| Description | Expansion Phone Controller |
| Category | Fire Fighter Telephones & Voice / Fire Fighter Telephones |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES, MINIPLEX transponders |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-1272
Firefighter telephone control module with three Class B telephone NACs for 4100ES systems. It adds telephone circuits in the main control panel or in transponders, and one is included with the 4100-1270 master telephone. The circuits can be converted to Class A with the 4100-1273 adapter.
Specifications
| Telephone circuits | Three Class B telephone NACs |
|---|---|
| Size | 1 block |
| Supervisory current | 80 mA |
| In use current | 140 mA + remote phones |
| Distance | 7500 ft (2286 m) distance to farthest phone, 18 AWG shielded twisted pair (STP) |
Used with
From Simplex datasheet S4100-1034. The datasheet can be downloaded under Documents above.
Your Dynamic Snippet will be displayed here...