Product details
| Part number | 4099-9708 |
|---|---|
| Description | Indoor English UL Cp IDNet |
| Category | Manual Call Points & Release Stations / Manual Call Points / Pull Stations |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4007ES (IDNet), 4010ES (IDNet), 4100ES (IDNet) |
| Approvals | UL listed; approved to UL 38 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4099-9708
Red break-glass manual call point, internal version, with a built-in IDNet addressable module (IAM) and an LED. Breaking the glass operates a micro-switch that reports the alarm to the panel; power and data come over the IDNet wire pair on one address. The supplied key opens the housing and tests the call point without breaking the glass.
The call point fits directly to a UK switch or socket box; a box depth of at least 25 mm is recommended.
Specifications
| Power and communications | IDNet, one address for each call point |
|---|---|
| Address setting | DIP switch, 8 position |
| Mounting | Surface or flush |
| Operating temperature | 14°F to 131°F or -10°C to 55°C |
| Humidity | Up to 90% RH non-condensing |
| Ingress protection | IP24D |
| Color | Red, RAL3001 |
| Dimensions (H x W x D) | 3 5/8 in. x 3 1/2 in. x 1 1/16 in. (93 mm x 89 mm x 27 mm) |
Used with
From Simplex datasheet A0001-0008. The datasheet can be downloaded under Documents above.