Skip to Content
Part no. 4098-XAD-210

Dual Zn Sampl Unt with Kit&sensor

1.15 SAR 1.15 SAR

  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4098-XAD-210
DescriptionDual Zn Sampl Unt with Kit&sensor
CategoryDetectors & Bases / Aspirating & Duct Sampling
System Simplex TrueAlarm detectors and TrueAlert appliances
Works with4007ES, 4008, 4010, 4010ES, 4100ES and 4100U (IDNet), Panels with MAPNET II communications
ApprovalsUL listed to Standard 268A; ULC listed to Standard S529; CSFM approved
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4098-XAD-210

Air aspiration duct smoke detection unit with two inlets and two TrueAlarm photoelectric sensors (one per inlet), supplied with the dual-inlet duct probe kit (LF-42243). A fan draws air from the duct through sampling tubes and a filter to the sensors, so the housing can be mounted away from the duct; it is the model for ducts wider than 90 in. (2286 mm). It reports over IDNet or MAPNET II with one address per sensor and needs a separate 24 VDC supply.

Dual-inlet duct detection needs three single-core flexible tubes, 25 ft or 50 ft each, ordered separately.

Specifications

Supply voltage18 VDC to 30 VDC supplied from fire alarm system
Current110 mA to 300 mA depending on fan speed; 680 mA in-rush
CommunicationsIDNet or MAPNET II communications, one address for each sensor
Sampling pipeRemote housing up to 82 ft (25 m) with rigid pipe, or 50 ft (15 m) with flexible tubing
Sensor sensitivity0.5% and 1.0% for each foot of obscuration, selectable at host control unit
Air velocity range0 to 4000 ft/min (0 to 1220 m/min)
Operating temperature range32°F to 122°F (0°C to 50°C)
Remote relaysSupervised control of up to 15 4098-9843 relays

Used with

  • LF-42288 – Sampling tube kit, two inlet tubes, ducts up to 27 in. (686 mm)
  • LF-42249 – 50 ft (15 m) flexible single-core tubing
  • LF-42283 – Dual-inlet water trap kit for humid environments
  • 2098-9806 – Remote test station with key switch and red LED
  • 4098-9843 – Remote relay, single Form C

From Simplex datasheet S4098-0048. The datasheet can be downloaded under Documents above.