Product details
| Part number | 4098-9788 |
|---|---|
| Description | 2 Wire Base with Remote LED |
| Category | Detectors & Bases / Detector Bases & Sounder Bases |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | Conventional 2-wire IDCs, 4090-9101 / 4090-9106 Zone Adapter Modules (IDNet or MAPNET II), 4090-5260 MX Zone Adapter Module, … |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9788
Two-wire base for Simplex 4098 conventional detectors, with screw terminals for the initiating device circuit (IDC). With smoke detectors such as the 4098-9602 it has connections for a remote alarm LED indicator; with the 4098-9612 to 4098-9615 heat detectors it is used without options. It is also the required mounting base for the 4098-9757 QuickConnect2 addressable sensor.
With heat detectors this base has no remote LED option; for a remote LED on a heat detector use the 4098-9684 base.
Specifications
| Connections | IDC and LED connections are screw terminals for in/out wiring, 18 to 14 AWG |
|---|---|
| Electrical box | 4" octagonal or 4" square, 1-1/2" deep; or single gang, 2" deep |
| Base height | 11/16" (17 mm) |
| Detectors per 4090-9101/9106 ZAM | Up to 20 |
Used with
- 4098-9602 – TrueAlarm photoelectric detector with TrueSense heat detection
- 4098-9601 – Photoelectric smoke detector
- 4098-9612 – Heat detector, 135° F (57° C) fixed temperature
- 4098-9757 – QuickConnect2 TrueAlarm sensor
- 4098-9832 – Adapter plate for surface boxes and 4" square flush boxes
From Simplex datasheet S4098-0017. The datasheet and installation manual can be downloaded under Documents above.