Product details
| Part number | 4098-9772 |
|---|---|
| Description | 520HZ Sounder Base |
| Category | Detectors & Bases / Detector Bases & Sounder Bases |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4007ES (IDNet), 4010ES (IDNet), 4100ES (IDNet), 4100U (IDNet) |
| Approvals | Listed to UL 268, UL 464 and ULC S529; UL, ULC, CSFM listed; FM approved |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9772
Addressable TrueAlarm sensor base with a built-in 520 Hz low-frequency sounder. It takes a TrueAlarm photoelectric, photo/heat multi-sensor or heat sensor (ordered separately) and uses a single IDNet address. The sounder needs separate 24 VDC system power or a NAC connection, and NAC power allows synchronized patterns such as Temporal or March Time.
The 4098-9772 must be flush mounted and needs a TrueAlarm sensor ordered separately.
Specifications
| Sounder output at 10 ft (3 m), 520 Hz | 80 dBA per UL 464; 86 dBA per UL 268 |
|---|---|
| Sounder voltage | 24 VDC nominal, 16 to 32 VDC from NAC |
| Alarm current (sounder on), 520 Hz | 129 mA at 16 V, 115 mA at 18 V |
| Communications | IDNet communications, 1 address for each base |
| Wiring | Screw terminals for in/out wiring, 18 to 14 AWG |
| UL listed temperature range | 32°F to 100°F or 0°C to 38°C |
| Humidity range | 10% to 95% RH |
| Housing color | Frost White |
Used with
- 4098-9714 – Photoelectric smoke sensor
- 4098-9754 – Multi-sensor, photoelectric and heat
- 4098-9733 – Heat sensor
- 4098-9863 – Adapter plate for 4 in. square electrical box
- 2098-9808 – Remote red LED alarm indicator
From Simplex datasheet S4098-0054. The datasheet can be downloaded under Documents above.