Skip to Content

Product details

Part number4098-9770
DescriptionCO Sensor Base Extended Life
CategoryDetectors & Bases / Detector Bases & Sounder Bases
System Simplex TrueAlarm detectors and TrueAlert appliances
Works with4007ES (IDNet, software 2.01.02 or higher), 4010ES (IDNet, software 2.01.02 or higher), 4100ES (IDNet, software 2.01.02 or higher), …
ApprovalsUL listed to UL 268 and UL 2075; ULC listed to CSA 6.19-01; CSFM listed (7300-0026:330); FM approved
AvailabilityIn stock in Riyadh
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4098-9770

IDNet sensor base, standard version without sounder, with a built-in electrolytic carbon monoxide (CO) sensing module. A TrueAlarm photoelectric, photo/heat or heat sensor head fits on it (ordered separately); the assembly uses one IDNet address and takes its power from the IDNet loop. The panel can use the CO reading for UL 2034 CO alarm, OSHA-level monitoring for ventilation control, or combined CO/smoke modes that reduce false alarms or detect fires faster.

A TrueAlarm photoelectric, photo/heat or heat sensor must be ordered separately, and the CO element (cartridge 4098-9747) must be replaced at the end of its 10-year life.

Specifications

Communications and powerIDNet communications, one address for each base
WiringScrew terminals for in/out wiring, 18 to 14 AWG (0.82 mm² to 2.08 mm²)
UL listed temperature range32° F to 100° F (0° C to 38° C)
Operating temperaturewith 4098-9733: 32° F to 122° F (0° C to 50° C); with 4098-9714 or 4098-9764: 15° F to 122° F (-9° C to 50° C)
Humidity range15 to 95% RH
CO sensor life10 year operational lifetime (5 years for 4100U FACUs); notices at 12 and 6 months
OSHA CO condition levelprogrammable, greater than 30 ppm
Housing colorFrost white

Used with

  • 4098-9714 – Photoelectric smoke sensor
  • 4098-9764 – Multi-sensor, photoelectric and heat
  • 4098-9733 – Heat sensor
  • 4098-9747 – CO replacement cartridge (CORC)
  • 4098-9832 – Adapter plate, required for surface mounted 4 in. electrical boxes

From Simplex datasheet S4098-0052. The datasheet, UL listing and installation manual can be downloaded under Documents above.