Product details
| Part number | 4098-9756 |
|---|---|
| Description | Duct Sensor Housing, 4-WIRE |
| Category | Detectors & Bases / Aspirating & Duct Sampling |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4007ES, 4008, 4010, 4010ES, 4020, 4100, 4100ES, 4100E, 4120, IDNet, MAPNET II, 2120 CDT on MAPNET II (relay operation not supported) |
| Approvals | UL listed to Standard 268A; UL, ULC, CSFM listed (CSFM 3240-0026.241); FM approved; MEA (NYC) acceptance MEA35-93E |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9756
The 4098-9756 is an addressable duct smoke sensor housing with a factory-installed 4098-9714 TrueAlarm photoelectric sensor. It samples air in air conditioning or ventilating ducts and sends analog smoke values to the panel over IDNet or MAPNET II. It also has a supervised output for up to 15 remote 4098-9843 relays under panel control; it needs separate 24 VDC and comes with one relay.
Order a sampling tube for the duct width separately; the relay output needs separate fused 24 VDC from the fire alarm power supply.
Specifications
| Input voltage | 18-32 VDC (24 VDC nominal) |
|---|---|
| Standby current | 3 mA @ 24 VDC |
| Alarm current | 15 mA @ 24 VDC; add 15 mA for each 4098-9843 relay |
| Relay control output | 4098-9843 relays only, 15 maximum; 500 ft (152 m) maximum; requires 4081-9008 10 k, 1/2 W end-of-line resistor |
| Sensor sensitivity | 0.2% to 3.7% per foot of obscuration, selectable at host control panel |
| Air velocity range | 300 to 4000 ft/min (91 to 1220 m/min) |
| UL listed temperature range | 32° F to 100° F (0° C to 38° C) |
| Duct size | Minimum 8” (203 mm) square or 18” (457 mm) diameter |
Used with
- 4098-9843 – Remote relay, single Form C (7 A @ 120 VAC); one included, up to 15
- 4081-9008 – End-of-line resistor harness, 10 k, 1/2 W, required for relay supervision
- 4098-9854 – Sampling tube for 12” (305 mm) ducts (other widths: 4098-9855 to 4098-9858)
- 2098-9806 – Remote test station with keyswitch and red LED
- 2098-9808 – Remote red LED status indicator
From Simplex datasheet 4098-0030. The datasheet can be downloaded under Documents above.