Product details
| Part number | 4098-9755 |
|---|---|
| Description | Duct Sensor Housing |
| Category | Detectors & Bases / Aspirating & Duct Sampling |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4007ES, 4008, 4010, 4010ES, 4020, 4100, 4100ES, 4100E, 4120, 2120 CDT (if configured for MAPNET II, TrueAlarm operation), IDNet or MAPNET II communications |
| Approvals | UL listed to UL 268A; ULC; CSFM (3240-0026.241); FM approved; MEA (NYC) MEA35-93E |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9755
The 4098-9755 is an addressable air duct smoke sensor housing with a factory-installed 4098-9714 TrueAlarm photoelectric sensor. Sampling tubes draw duct air past the sensor; the panel reads its analog value, sets the sensitivity (0.2% to 3.7% per foot) and tracks dirt build-up. This basic model has no relay output and is powered from the IDNet or MAPNET II loop.
A sampling tube sized to the duct width (4098-9854 to 4098-9858) must be ordered separately, and duct smoke detection does not replace smoke detection in open areas.
Specifications
| Data communications | IDNet or MAPNET II communications, auto-select, one address per housing; provides operating power to model 4098-9755 |
|---|---|
| Sensor sensitivity range | 0.2% to 3.7% per foot of obscuration, selectable at host control panel |
| Air velocity range | 300 to 4000 ft/min (91 to 1220 m/min) |
| UL listed temperature range | 32° F to 100° F (0° C to 38° C) |
| Operating temperature range | 32° F to 122° F (0° C to 50° C) |
| Humidity range | 10% to 95% RH, non-condensing |
| Wiring connections | Terminal blocks, 18 to 12 AWG (0.82 mm² to 3.31 mm²) |
| Duct size | Rectangular or round ducts; minimum 8” (203 mm) square or 18” (457 mm) diameter |
Used with
- 4098-9854 – Sampling tube for 12” (305 mm) duct width
- 4098-9855 – Sampling tube for 13” to 23” (330 mm to 584 mm) duct width
- 4098-9856 – Sampling tube for 24” to 46” (610 mm to 1168 mm) duct width
- 2098-9808 – Remote red LED status indicator, single-gang stainless steel plate
- 2098-9806 – Remote test station with keyswitch and red LED