Product details
| Part number | 4098-5680 |
|---|---|
| Description | Conventional 2-WIRE Relay Base |
| Category | Detectors & Bases / Detector Bases & Sounder Bases |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | Conventional 2-wire IDCs |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-5680
2-wire 5 in. base for Simplex conventional smoke and heat detectors, with an auxiliary alarm relay (dual form C) and connections for a remote LED indicator. The relay module mounts in the base electrical box.
It must be the only device connected on the IDC for the relay to operate.
Specifications
| Circuit | 2-wire |
|---|---|
| Base size | 5 in. |
| Relay | Dual form "C", for suppressed loads |
| Relay rating | Power limited, 1 A @ 28 VDC; Non-power limited, 1/2 A @ 120 VAC |
| Wiring | Relay contacts and IDC (-), color coded 18 AWG leads; IDC (+) and LED wiring, screw terminals for 18 to 14 AWG |
| Electrical box | 4 in. octagonal or 4 in. square, 1-1/2 in. deep, with 1-1/2 in extension ring |
Used with
- 4098-5602 – Photo-Heat detector listed to UL
- 4098-5601 – Photo detector listed to UL
- 4098-5610 – Heat detector, 135°F (57.2°C) fixed temperature and rate-of-rise
- 4098-5612 – Heat detector, 200°F (93.3°C) fixed temperature
- 4098-9799 – 6 in. adapter plate
From Simplex datasheet S4098-0059. The datasheet can be downloaded under Documents above.