Product details
| Part number | 4098-5267 |
|---|---|
| Description | Heat Sensor with Reed S |
| Category | Detectors & Bases / Smoke, Heat & Multi Sensors |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4100ES (MX Loop Module), 4010ES (MX Loop Module), 4007ES (MX Loop Module) |
| Approvals | UL listed; heat sensors listed to UL 521 |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-5267
The 4098-5267 is an MX addressable heat sensor with a built-in isolator. It sends analog temperature readings to the control unit, where the alarm is set to 135°F (57°C) or 200°F (93°C), with or without rate-of-rise. It works with Simplex 4100ES, 4010ES and 4007ES control units fitted with an MX Loop Module.
For indoor use only; remove the supplied dust cover when the system is commissioned.
Specifications
| Heat settings (at control unit) | 135°F (57°C) or 200°F (93°C) either with or without rate-of-rise detection |
|---|---|
| Rate-of-rise | 15°F (8.4°C) a minute |
| Current | 350 µA supervisory; 4.0 mA maximum in alarm |
| Max. ceiling ambient | 100°F (38°C) at 135°F (57.2°C) setting; 150°F (65.6°C) at 200°F (93°C) setting |
| Storage temperature | -22°F to 158°F (-30°C to 70°C) |
| Humidity | Up to 93% RH non-condensing |
| IP rating | IP44 in accordance with BS EN 60529:1992 + A2:2013 |
| Dimensions | 108 mm x 42 mm (4.252 in. x 1.653 in.) |
Used with
- 4098-5260 – 4 in. continuity base 4B-C
- 4098-5217 – Addressable loop-powered sounder base
- 4098-5220 – Addressable loop-powered sounder-beacon base
- 2098-9808 – Remote LED alarm indicator
- 4098-5276 – Address flags (pack of 100)
From Simplex datasheet S4906-0017. The datasheet and UL listing can be downloaded under Documents above.