Part no. 4098-5214

Duct Housing, NO Relay/Detector

832.60 SAR 832.60 SAR

  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4098-5214
DescriptionDuct Housing, NO Relay/Detector
CategoryDetectors & Bases / Aspirating & Duct Sampling
System Simplex TrueAlarm detectors and TrueAlert appliances
Works with4100ES (MX Loop Module), 4010ES (MX Loop Module), 2050 Foundation Series (MX Loop Module), 2250 Foundation Series (MX Loop Module)
ApprovalsUL listed to UL 268A; ULC; CSFM
AvailabilityIn stock in Riyadh
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4098-5214

Duct smoke sensor housing that lets a 4098-5252 or 4098-5292 MX photoelectric sensor monitor air conditioning or ventilation ducts. A sampling tube sized to the duct width brings duct air to the sensor, and an exhaust tube returns it to the duct. The sensor and sampling tube are ordered separately; the clear cover allows visual inspection.

Duct smoke detection does not replace the smoke detection required for open areas.

Specifications

Dimensions (H x W x D)10 in. x 8 1/2 in. x 2 1/4 in. (254 mm x 216 mm x 57 mm)
Air velocity500 ft/min to 4,000 ft/min (2.54 m/sec to 20.3 m/sec)
Intake/exhaust pressure differentialbetween 0.016 in. (0.4 mm) and 1.0 in. (25.4 mm) of water
UL listed temperature range32°F to 100°F (0°C to 38°C)
Humidity range10% to 85% RH, non-condensing
CommunicationsMX Loop, one address for each sensor base
Wiring connectionsTerminal blocks, 18 AWG to 14 AWG
Includedinternally mounted sensor base, 7 in. (178 mm) exhaust tube, sampling tube end plug, mounting screws, mounting template

Used with

  • 4098-5252 – 850 series MX photoelectric sensor for the 4098-5214
  • 4098-5292 – MX photo sensor with address switch
  • STS-2.5 – Sampling tube, 30 in., for 12 in. to 30 in. ducts
  • STS-5.0 – Sampling tube, 60 in., for 30 in. to 60 in. ducts
  • 2098-9808 – Remote red alarm LED