Product details
| Part number | 4098-5211 |
|---|---|
| Description | 4 Wire Sounder Base |
| Category | Detectors & Bases / Detector Bases & Sounder Bases |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4100ES (MX Loop), 4010ES (MX Loop), 4100U (MX Loop) |
| Approvals | UL listed |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-5211
Sounder base for MX Technology sensors that is switched on from the MX Loop but powered from a separate 24 VDC fire alarm power supply through its own wiring loop. It gives up to 90 dBA at 10 ft (3 m), with eight local tones selected by DIP switch and volume adjustable at the base.
It needs a separate 24 VDC power wiring loop in addition to the MX Loop.
Specifications
| Power | Separate 24 VDC fire alarm power supply through a separate wiring loop |
|---|---|
| Sounder base voltage | 18 to 32 VDC from fire alarm power supply. 24 VDC is nominal |
| Maximum sound output | 90 dBA at 10 ft (3 m) |
| Current | 5 µA supervisory; 20 µA from MX Loop; 20 mA from external 24 VDC power at full volume |
| Tones | Eight tone selections, DIP switch selected at the base |
| Operating temperature | 0° to 38° C (32° to 100° F) |
| Size with sensor mounted | 110 mm x 68.5 mm (4 11/32 in. x 2 11/16 in.) |
| Installation instructions | 579-926 |
Used with
- 4098-5201 – MX heat sensor
- 4098-5202 – MX photoelectric smoke sensor
- 4098-5203 – MX photoelectric smoke sensor with heat sensor
- 517.050.015 – Volume Trimmer Tool
From Simplex datasheet S4098-0045. The datasheet can be downloaded under Documents above.