Skip to Content
Part no. 4098-5209

Lp Sounder Base 85DB@3FT

1.15 SAR 1.15 SAR

  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4098-5209
DescriptionLp Sounder Base 85DB@3FT
CategoryDetectors & Bases / Detector Bases & Sounder Bases
System Simplex TrueAlarm detectors and TrueAlert appliances
Works with4100ES with MX Loop Module, 4010ES with MX Loop Module, 4100U with MX Loop Module
ApprovalsUL listed
AvailabilityIn stock in Riyadh
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4098-5209

Non-addressable, low-output sounder base for MX Technology smoke and heat sensors, powered from the MX Loop with no separate power wiring. It gives up to 85 dBA at 3 ft (1 m) and draws up to 6.8 mA from the loop in alarm. One of eight local tones is set by DIP switch at the base, and the volume can be reduced with a trimmer tool.

For supplemental use only; it does not replace the building's notification appliances.

Specifications

PowerMX Loop powered, no separate power connection is required
Maximum sound output85 dBA at 3 ft (1 m)
Supervisory current200 µA
Activated current6.8 mA at full volume of 85 dB at 3 ft (1 m); 1.2 mA at low volume
TonesEight local tone selections, DIP switch selected at the base
Size with sensor fitted110 mm x 68.5 mm (4 11/32 in. x 2 11/16 in.)
Humidity rangeUp to 93% RH at 32° C (90° F), for indoor use only

Used with

  • 4098-5202 – MX photoelectric smoke sensor
  • 4098-5203 – MX photoelectric sensor with heat sensing
  • 4098-5201 – MX heat sensor; 200°F (93°C) setting not for this base
  • 2098-9808 – Remote LED alarm indicator
  • 517.050.015 – Volume Trimmer Tool

From Simplex datasheet S4098-0045. The datasheet, UL listing and installation manual can be downloaded under Documents above.