Product details
| Part number | 4090-9008 |
|---|---|
| Description | Dual Relay IAM, IDNet |
| Category | Addressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators) |
| System | Simplex fire alarm systems |
| Works with | 4007ES (IDNet), 4010ES (IDNet), 4100ES (IDNet), 4100U (IDNet), 4100/4100U/4100ES, 4120, 4020, 2120 CDT (MAPNET II) |
| Approvals | UL listed to UL 864; ULC; CSFM; FM approved |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4090-9008
An addressable relay module (IAM) with two Form C (DPDT) contacts, rated 2 A at 30 VDC resistive, controlled and tracked as one address. It works on IDNet or MAPNET II and takes its power from the communication line. Typical uses are switching local power for elevator capture, HVAC components, pressurization fans and dampers.
Contacts are not rated for incandescent lamp switching; add external transient suppression where the load needs it.
Specifications
| Communications | IDNet or MAPNET II communications, 1 address per device |
|---|---|
| Power | Supplied by communications |
| Contacts | Dual Form C contacts (DPDT) |
| Power-limited rating | 2 A @ 30 VDC, resistive; 1 A @ 30 VDC, inductive |
| Nonpower-limited rating | 0.5 A @ 125 VAC, resistive |
| Wire connections | Screw terminals, 18 to 14 AWG wire (0.82 to 2.08 mm²) |
| Dimensions | 4 ⅛” H x 4” W x 1 ⅜” D (105 mm x 102 mm x 35 mm) |
| Temperature range | 32° to 120° F (0° to 49° C), intended for indoor operation |
Used with
- 4090-9813 – Adapter plate for 4 11/16” square electrical box
- 4090-9801 – Trim plate with LED viewing window, semi-flush box
- 4090-9802 – Trim plate with LED viewing window, surface box
- 2081-9044 – Overvoltage protector
From Simplex datasheet S4090-0014. The datasheet can be downloaded under Documents above.