Skip to Content
Part no. 4090-9007

Addressable Signal ZAM

287.50 SAR 287.50 SAR

  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4090-9007
DescriptionAddressable Signal ZAM
CategoryAddressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators)
System Simplex fire alarm systems
Works with4007ES, 4008, 4010ES, 4100ES, 4100U (software revision 11.11.01 or higher), IDNet
ApprovalsUL listed to Standard 864; UL, ULC, CSFM listed; FM approved; MEA (NYC) acceptance
AvailabilityIn stock in Riyadh
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4090-9007

The 4090-9007 Signal IAM is an IDNet addressable module that adds a supervised notification appliance circuit (NAC) under panel control. On command it connects a separate 24 VDC NAC input, or a 25 or 70.7 VRMS audio input, to its output for local notification zones; the module itself is powered by the IDNet loop. It mounts in a standard 4 in. square electrical box.

It does not work with SmartSync two-wire horn/strobe control, TrueAlert addressable control or 4010 panel IDNet; use four-wire horn/strobe appliances.

Specifications

CommunicationsIDNet communications, one address
Channel loadingConsumes two unit loads; each Signal IAM reduces the IDNet loop capacity by two addresses
NAC inputNominal 24 VDC from FACU NAC or NAC extender; 25 VRMS or 70.7 VRMS from compatible listed audio source
NAC output0.5 A for special application or regulated 24 VDC appliances; speakers 0.5 A at 25 VRMS (12.5 W) or 70.7 VRMS (35 W)
Output wiringClass B or Class A; Class B uses 4081-9008 end-of-line resistor, 10 Kohm, 1/2 W
Wire connectionsScrew terminals for in/out wiring, 18 to 12 AWG wire (0.82 mm² to 3.31 mm²)
Dimensions4 in. x 4 1/8 in. x 1 1/4 in. D (102 mm x 105 mm x 32 mm)
Temperature range32° to 120° F (0° to 49° C) indoor operation only

Used with

  • 4081-9008 – End-of-line resistor for Class B NAC output, 10 Kohm, 1/2 W
  • 4090-9801 – Trim plate with LED window, semi-flush box
  • 4090-9802 – Trim plate with LED window, surface box
  • 4090-9122 – IDNet Isolator2, may be required for loop connections
  • 2081-9044 – Overvoltage protector, required where wiring exits and enters a building

From Simplex datasheet S4090-0010. The datasheet, UL listing and installation manual can be downloaded under Documents above.