Product details
| Part number | 4090-9007 |
|---|---|
| Description | Addressable Signal ZAM |
| Category | Addressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators) |
| System | Simplex fire alarm systems |
| Works with | 4007ES, 4008, 4010ES, 4100ES, 4100U (software revision 11.11.01 or higher), IDNet |
| Approvals | UL listed to Standard 864; UL, ULC, CSFM listed; FM approved; MEA (NYC) acceptance |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4090-9007
The 4090-9007 Signal IAM is an IDNet addressable module that adds a supervised notification appliance circuit (NAC) under panel control. On command it connects a separate 24 VDC NAC input, or a 25 or 70.7 VRMS audio input, to its output for local notification zones; the module itself is powered by the IDNet loop. It mounts in a standard 4 in. square electrical box.
It does not work with SmartSync two-wire horn/strobe control, TrueAlert addressable control or 4010 panel IDNet; use four-wire horn/strobe appliances.
Specifications
| Communications | IDNet communications, one address |
|---|---|
| Channel loading | Consumes two unit loads; each Signal IAM reduces the IDNet loop capacity by two addresses |
| NAC input | Nominal 24 VDC from FACU NAC or NAC extender; 25 VRMS or 70.7 VRMS from compatible listed audio source |
| NAC output | 0.5 A for special application or regulated 24 VDC appliances; speakers 0.5 A at 25 VRMS (12.5 W) or 70.7 VRMS (35 W) |
| Output wiring | Class B or Class A; Class B uses 4081-9008 end-of-line resistor, 10 Kohm, 1/2 W |
| Wire connections | Screw terminals for in/out wiring, 18 to 12 AWG wire (0.82 mm² to 3.31 mm²) |
| Dimensions | 4 in. x 4 1/8 in. x 1 1/4 in. D (102 mm x 105 mm x 32 mm) |
| Temperature range | 32° to 120° F (0° to 49° C) indoor operation only |
Used with
- 4081-9008 – End-of-line resistor for Class B NAC output, 10 Kohm, 1/2 W
- 4090-9801 – Trim plate with LED window, semi-flush box
- 4090-9802 – Trim plate with LED window, surface box
- 4090-9122 – IDNet Isolator2, may be required for loop connections
- 2081-9044 – Overvoltage protector, required where wiring exits and enters a building
From Simplex datasheet S4090-0010. The datasheet, UL listing and installation manual can be downloaded under Documents above.