Product details
| Part number | 4010-9915 |
|---|---|
| Description | Bacpac Grid Connect Module |
| Category | Network, Annunciators & Software / Network & Fiber Media Cards |
| System | Simplex 4010ES fire alarm panels |
| Works with | 4010ES, BACnet IP / BACnet MS/TP, Modbus TCP / Modbus RTU, Metasys |
| Approvals | UL, ULC, CSFM listed; UL listed to Standard 864; ULC listed to Standard S527 |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4010-9915
Module that converts status information from a 4010ES fire alarm control unit into BACnet or Modbus protocol for building automation systems. It connects to Port B of a 4010-9918 RS-232 module and outputs Ethernet (BACnet IP or Modbus TCP) or RS-485 serial data (BACnet MS/TP or Modbus RTU). It handles up to 1500 points and needs no device address.
The 4010-9918 RS-232 module and the Ethernet LAN cable are ordered separately.
Specifications
| Maximum points | 1500 |
|---|---|
| Module size | Single block module (4 x 5) |
| Input power | 24 VDC from FACU; operation range 9 VDC to 30 VDC |
| Current | 123 mA maximum from 24 VDC FACU supply |
| Data output | BACnet IP or Modbus TCP (Ethernet); BACnet MS/TP or Modbus RTU (serial) |
| Required RS-232 module | 4010-9918 |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
| Humidity | Up to 93% RH, non-condensing @ 90°F (32°C) maximum |
Used with
- 4010-9918 – RS-232 module (the BACpac connects to its Port B)
From Simplex datasheet S4100-0051. The datasheet can be downloaded under Documents above.