Skip to Content
Part no. 4010-9505

1 Bay, 2x40, 1 ESMX, 220/240V, Red

14,763.70 SAR 14,763.70 SAR

14,763.70 SAR incl. VAT
  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4010-9505
Description1 Bay, 2x40, 1 ESMX, 220/240V, Red
CategoryFire Alarm Control Panels / 4010ES Panels
System Simplex 4010ES fire alarm panels
Works withMX Loop addressable devices (ESMX Loop channel), Simplex ES Net network (optional NIC), Simplex 4120 network (optional NIC), …
ApprovalsUL listed (4010ES series: UL 864 Control Units, System)
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4010-9505

The 4010-9505 is a 4010ES addressable fire alarm basic control unit in a red one-bay cabinet, with an English 2x40 LCD operator interface. It has one ESMX Loop channel, Class A or B, for up to 250 addressable MX Loop points, and runs on 220 VAC to 240 VAC. The unit includes an 8 A power supply, four 3 A NACs and three 4 in. x 5 in. option blocks for added modules.

The one-bay cabinet holds batteries up to 33 Ah and is limited to three option block spaces in total.

Specifications

Operator interface2x40 LCD Operator Interface
Addressable channel(1) ESMX Loop Channel, Class A or B, up to 250 addressable MX Loop points
Language and voltageEnglish 220 VAC to 240 VAC
Supervisory / alarm current364 mA / 432 mA
Option blocksThree 4 in. x 5 in. block
Power supply8 A power supply with up to 2 A of auxiliary power
NACs4 onboard Class A or B, 3 A NACs
Battery capacity (one-bay cabinet)33 Ah max in one bay control cabinet

Used with

  • 4010-6312 – ESMX optional loop mezzanine card
  • 4010-9911 – Alarm relay module, mounts on Main System Supply (one max)
  • 4010-9910 – City Connect module, mounts on Main System Supply (one max)
  • 4606-9102 – 4010ES RUI LCD annunciator, English
  • 4100-5128 – Battery distribution terminal block, needed when battery wiring leaves the box