Product details
| Part number | 4009-9705 |
|---|---|
| Description | 4009 IDNAC Extender, Red |
| Category | Fire Alarm Control Panels / NAC Extenders & Repeaters |
| System | Simplex fire alarm systems |
| Works with | 4007ES (RUI, maximum one), 4100ES (RUI, up to 31), 4017ES (RUI, maximum one) |
| Approvals | UL, ULC, and CSFM listed; UL 864 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4009-9705
4009 IDNAC Extender in a red cabinet: a remote power unit with one 3 A IDNAC SLC for TrueAlert and TrueAlert ES addressable notification appliances. The IDNAC output is held at 29 VDC in alarm, also on battery, and the unit adds up to 2 A auxiliary power or simple NAC output and a battery charger. It connects to 4007ES, 4100ES and 4017ES panels over RUI; AC input is 120 VAC or 240 VAC, 50 Hz or 60 Hz, auto-select.
A 4007ES or 4017ES panel supports only one 4009 IDNAC Extender; a 4100ES supports up to 31.
Specifications
| Cabinet color | Red |
|---|---|
| IDNAC SLC | One 3 A IDNAC SLC |
| Total power | 4 A total from all outputs in alarm |
| AUX power/Simple NAC | 2 A special applications Aux or SNAC, programmable |
| AC input | 120 V (50 Hz or 60 Hz): 2 A; 240 V (50 Hz or 60 Hz): 1 A |
| Battery charging | Up to 12.7 Ah internally; up to 33 Ah in an external cabinet |
| AUX relay | Form C dry contacts, 2 A at 32 VDC and 30 VAC, resistive load |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
Used with
- 2081-9288 – 12.7 Ah battery, 12 VDC, fits in the cabinet (two required)
- 2081-9287 – 25 Ah battery, 12 VDC, needs an external battery cabinet (two required)
- 2081-9276 – 33 Ah battery, square, 12 VDC, needs an external battery cabinet
From Simplex datasheet S4009-0006. The datasheet can be downloaded under Documents above.