Product details
| Part number | 2084-9003 |
|---|---|
| Description | Phone with Door & Trim Flush Mount |
| Category | Fire Fighter Telephones & Voice / Fire Fighter Telephones |
| System | Simplex fire alarm systems |
| Works with | 4100ES firefighter telephone control, 4100U, Legacy 4100/4120 firefighter telephone controls |
| Approvals | UL listed (UL 864); FM approved; CSFM; MEA (NYC); agency listed as type 4590-B |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2084-9003
Firefighter telephone assembly for flush mounting: phone, mounting plate and red door with trim, marked LOCAL FIRE EMERGENCY PHONE. The door has a standard lock (no break-rod) and the handset is the standard, non-armored type. It connects to the supervised two-wire phone circuit of a Simplex firefighter telephone control.
Order the 2975-9053 backbox separately; one is needed for each phone assembly.
Specifications
| Mounting | Flush |
|---|---|
| Door | Locked door, no break-rod |
| Door marking | LOCAL FIRE EMERGENCY PHONE |
| Phone | Standard handset (not armored, no push-to-talk) |
| Door and trim | Red, white silk-screened lettering |
| Door trim size | 11 11/16 in. (305 mm) W x 15 in. (381 mm) H |
| Backbox | 2975-9053, 13 in. H x 9 11/16 in. W x 3 1/2 in. D (330 mm x 243 mm x 89 mm), ordered separately |
| Agency type number | 4590-B |
Used with
- 2975-9053 – Red backbox, one per phone assembly (required)
- 4081-9008 – 10 kΩ end-of-line resistor harness, one per Class B phone circuit
From the manufacturer's documentation. The datasheet can be downloaded under Documents above.