Product details
| Part number | 2081-9296 |
|---|---|
| Description | Battery 50AH Lead Acid |
| Category | Power Supplies & Batteries / Batteries & Battery Cabinets |
| System | Simplex fire alarm systems |
| Works with | 4100ES / 4100U (2 or 3 bay), 4010ES (2 bay), 4004R and 4010 (4081 series cabinet with charger), 4100 and 4120 (external cabinet) |
| Approvals | Meets UL, ULC and Factory Mutual requirements for use with the respective Simplex battery chargers |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2081-9296
Rechargeable 12 V, 50 Ah sealed lead-acid battery for Simplex fire alarm control panels, used in pairs wired in series for 24 V. It fits inside 2-bay or 3-bay 4100ES/4100U cabinets and 2-bay 4010ES cabinets; 4004R and 4010 panels use a 4081 series cabinet with charger, and 4100/4120 panels need an external cabinet. The sealed construction needs no added water.
Use two identical batteries (same model, appearance and about the same date of manufacture) wired in series for 24 V.
Specifications
| Capacity (20 hour rate) | 50 Ah |
|---|---|
| Nominal voltage | 12 V |
| Width x depth x height | 9 in. (229 mm) x 5-1/2 in. (140 mm) x 8 7/8 in. (225 mm) |
| Approximate weight | 41.8 lb (19 kg) |
| Typical charge/discharge cycles | 100 cycles to 150 cycles |
| Preferred charge temperature | 60°F to 90°F (15.6°C to 32.2°C) |
Used with
- 2081-9281 – Battery cabinet without charger, beige, for 50 Ah batteries
- 2081-9282 – Battery cabinet without charger, red, for 50 Ah batteries
- 4081-9301 – Battery cabinet with charger for 4010 and 4004R
- 4081-9306 – Battery cabinet with charger for 4100ES, 4010ES and 4100U
- 2081-9298 – Seismic battery bracket, 4100ES/4100U 3 bay cabinet
From Simplex datasheet S2081-0006. The datasheet can be downloaded under Documents above.