Product details
| Part number | 2080-9070 |
|---|---|
| Description | Maintenance Disc Switch Surface |
| Category | Manual Call Points & Release Stations / Abort & Maintenance Switches |
| System | Simplex fire alarm systems |
| Works with | 4010ES releasing systems (RAC) |
| Approvals | UL, ULC, CSFM listed |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2080-9070
Keyswitch-operated maintenance disconnect switch for fire suppression releasing appliance circuits (RACs), surface mounted in the included red box, without indicator lamp. In the disabled position it opens the output circuit and places a 16.2 kΩ resistor across the input to signal a supervisory condition at the panel.
One maintenance switch is required for every releasing appliance circuit (RAC); maintenance switches are not FM approved.
Specifications
| Mounting | Surface mount; includes red mounting box |
|---|---|
| Size | Single-gang; stainless steel single gang plate |
| Keyswitch | Maintained position keyswitch with key removable only in the normal position |
| Contact block | 3 position contact block housing with 1 contact block installed |
| Contacts | Silver contacts; 1 normally open & 1 normally closed; rated 2 A resistive @ 30 VDC |
| Disabled position | Opens connection to output and places a 16.2 kΩ resistor across the input circuit |
| Wiring | 18 AWG (0.82 mm²) color coded wire leads for suppression circuit |
| Temperature | 32° F to 120° F (0° C to 49° C) |
Used with
- 2080-9061 – Additional contact block, 1 Form C
- 4090-9005 – Suppression Release Peripheral
- 2081-9046 – Coil Supervision Module
- 2080-9069 – Flush mount version
From Simplex datasheet S2080-0010. The datasheet can be downloaded under Documents above.